Could you please explain that logic?
Furthermore;
seismic inter-story drift is limited to 2.5% of story height. If story height is 3.5m, the allowable inter-story drift is 87.5mm. If all floors were to be within the drift (so code requirements are satisfied) then a 10 story free standing building would have total roof drift of 87.5mmx10=87.5cm. Thats a lot, yes.
But I do not see any limits in code for the seismic total drift as long as you have satisfied the inter-story drifts.
Ofcourse, more the building overall drift, more will be p-delta effects, (that could be huge for a massive tall building).
In wind design, overall drift is limited due to problem of acceleration at top floors. But in a seismic event, obviously human criteria is not something you should aim for.