  1. Why do you have just one joint assigned as support under the wall? The wall should be meshed and supports should be assigned under each node. Thanks.
    1 point
  2. W/Salaam, The error message is there because of violation of UBC Clause that requires Pu/Po<0.35. I would suggest that you beef up your walls to get the error message clear. Also, have a look at the attached documents. Thanks. Shear Wall Design Manual- Technical Notes.pdf Tall Buildings Shear Walls.pdf